Checks a post-tensioned (bonded or unbonded) or pre-tensioned slab, one-way on walls or a flat slab on columns, to SIA 262:2025, in design order: the tendons and their force with every loss, the stresses, cracks and deflection, the bending and punching resistance and the anchorage at the edge. Every step shows its formula and the clause it comes from.

Pro SIA 262:2025

Part of the Pro plan

This module is included in the Pro plan and above, with its calculation note.

About this check

clauses, worked example and questions

Checks a post-tensioned (bonded or unbonded) or pre-tensioned slab, one-way on walls or a flat slab on columns, to SIA 262:2025, in design order: the tendons and their force with every loss, the stresses, cracks and deflection, the bending and punching resistance and the anchorage at the edge. Every step shows its formula and the clause it comes from.

What it checks

  • Tendons in the strip: ap,c = ηp · Ap/bc and ap,m = (1 − ηp) · Ap/bm; fpd = fp0,1k/γs, equation (5).
  • Steel stresses: equations (21) and (22), clauses 4.1.5.2.1 and 4.1.5.2.2, and σp∞ ≥ 0.45 · fpk, clause 4.1.5.2.3.
  • Losses: friction, clause 4.1.5.3.3, equation (24); anchor slip and elastic shortening, clause 4.1.5.3.1; relaxation Δσpr = 3 · ρ1000 · σp0 (clause 3.3.2.7.1); creep, shrinkage and relaxation by EN 1992-1-1 equation (5.46) (clause 4.1.5.3.4).
  • Equivalent loads u per span (clause 4.1.5.1.1) and the secondary moments MP,s,∞ over the supports, clause 4.1.5.1.3.
  • Concrete at transfer: fck(t) ≥ 0.3 · fck and |σc| ≤ 0.6 · fck(t), clause 4.1.5.2.4, equation (23), in the column and the middle strip.
  • Cracks: service stresses against fct,eff (clause 4.4.1.3), and σs,r against Table 17 in each span and over each support (clause 4.4.2.3.10).
  • Long-term deflection: w∞ = (1 + φ) · ∬ (Mg + ψ2 · Mq + MP,∞)/(Ecm · Ic), clause 4.4.3.2.4, equation (103), against l/wadm per span (clause 4.4.3.2.1), and the camber w0 at transfer.
  • Bending per strip: md ≤ mRd with the bars and the bonded tendons (clause 4.2.1.5), Mcr ≤ MRd (clause 4.3.1.2) and x/d ≤ 0.5 · 435/fyd (clause 4.1.4.2.6). Md includes MP,s with γP = 1.0 (clauses 4.1.5.5.2 and 4.1.5.1.4).
  • Punching at an interior column without punching reinforcement: Vd = Rd − qd · A − VP (clause 4.3.6.2.6), with VP from the tendons crossing the control section; ψ by equation (60) at level 2 with the decompression moment mDd (clause 4.3.6.4.3); Vd ≤ VRd,c = kr · τcd · dv · u, clause 4.3.6.3.1, equation (58).
  • Anchorage at the edge: Pd,1 = 1.2 · Pmax,1 (clause 4.1.5.5.3), the bursting through the thickness against the links, and the splitting forces Th,1 and Tb in the plane of the slab, clause 5.3.3.

What you enter and what you get

You enter the kind of slab, up to four spans, for a flat slab ly, bc, ψs and ψf, the thickness h, the bars, the loads, the concrete at 28 days and at transfer, and the steels. For the prestress: the type, the number of tendons and their layout across the strip, the profile yE, yM, yS, λ and ξ, and the tensioning data. Then the crack requirements, the deflection limit, the load factors, the interior column and the anchors at the edge.

You get the tendon force at the key sections, every stress, deflection and check with its utilisation and clause, and the reinforcement for the anchorage. With the Pro plan, it prints as an A4 calculation note.

Assumptions and limits

  • A one-way slab is checked on a strip 1 m wide. A flat slab is checked one direction at a time, on its design strip, like a continuous beam on the column lines carrying the whole load.
  • The column strip takes ψs of the support moment and ψf of the span moment, from your plate analysis.
  • Mid-panel deflection is about that of the column strip in one direction plus the middle strip in the other: check both directions and add.
  • Deflection uses the uncracked gross section, creep by (1 + φ).
  • Punching is checked at the interior column line with the largest support force. Edge and corner columns need the punching module. Protect against progressive collapse (clauses 4.3.6.1.3 and 4.3.6.7).
  • The approval of the prestressing system governs the anchor itself (clauses 4.1.5.1.7 and 4.1.5.2.5).

Worked example

A flat slab on columns, three spans of 7.0, 7.5 and 7.0 m, a design strip of 7.5 m with a 3.5 m column strip, h = 280 mm, fck = 35 N/mm², four bonded tendons of 600 mm², 75 % in the column strip, tensioned from both ends, g2 = 2 kN/m², q = 3 kN/m², 500 × 500 mm interior columns and a limit of l/300. These are the module's own results for its worked example, computed when this page was built.

Inputs
InputValueRef.
Kind of slabFlat slab on columns — one direction
Number of spans n3
Span 1 l17 m
Span 2 l27.5 m
Span 3 l37 m
Width of the design strip (span across) ly7.5 m
Width of the column strip bc3.5 m
Share of the support moment in the column strip ψs0.7
Share of the span moment in the column strip ψf0.6
Slab thickness h280 mm
Bottom bars: diameter Øb12 mm
Bottom bars: spacing sb200 mm
Bottom bars: distance from the face to their centre yb30 mm
Top bars over the columns (column strip): diameter Øt16 mm
Top bars over the columns: spacing st150 mm
Top bars: distance from the face to their centre yt30 mm
Top bars of the middle strip over the supports: diameter Øt,m12 mm
Top bars of the middle strip: spacing st,m200 mm
Additional permanent load g22 kN/m²
Imposed load q3 kN/m²
Quasi-permanent factor of the imposed load ψ20.3
Characteristic compressive strength fck35 N/mm²§ 3.1.2.2.2
Ultimate compressive strain εc2d3.0 ‰§ 4.2.1.5
Mean tensile strength fctm3.2 N/mm²§ 3.1.2.2.4
Modulus of elasticity Ecm34000 N/mm²§ 3.1.2.3.3
Unit weight of the reinforced concrete γ25 kN/m³
Largest aggregate size Dmax32 mm§ 4.3.3.2.1
Compressive strength at transfer fck(t)25 N/mm²§ 4.1.5.2.4
Mean tensile strength at transfer fctm(t)2.6 N/mm²
Modulus of elasticity at transfer Ecm(t)30000 N/mm²
Characteristic yield strength fyk500 N/mm²
Modulus of elasticity Es205000 N/mm²
Resistance factor for concrete γc1.5§ 2.4.2.6
Resistance factor for steel γs1.15§ 2.4.2.6
Duration factor ηt1.0 — both conditions of 4.2.1.3 met§ 4.2.1.3
Type of prestressingPost-tensioned, grouted (bonded)
Number of tendons in the design strip np4
Layout across the stripPartly banded
Share of the tendons in the column strip ηp0.75
Area of one tendon Ap1600 mm²
Characteristic tensile strength fpk1860 N/mm²§ 3.3.2.2
Characteristic 0.1 % proof stress fp0,1k1640 N/mm²§ 3.3.2.2
Modulus of elasticity Ep195000 N/mm²§ 3.3.2.4
Relaxation loss after 1000 hours ρ10002.5 %§ 3.3.2.7.1
Height of the flat duct ØH22 mm
Height at the end anchors yE140 mm
Height at the low points yM50 mm
Height over the interior supports yS225 mm
Length of the reverse curve, as a fraction of the span λ0.1
Low point in the end spans, from the end support ξ0.4
Stress at the jack σp,max1395 N/mm²§ 4.1.5.2.1
Tendons tensionedFrom both ends
Friction coefficient μ0.18§ 4.1.5.3.3
Unintentional angular deviation Δφ0.005 rad/m§ 4.1.5.3.3
Slip at the anchor (wedge draw-in) Δls6 mm§ 4.1.5.3.1
Final creep coefficient φ(∞,t0)2.0§ 3.1.2.6.2
Final shrinkage strain εcs,∞0.3 ‰§ 3.1.2.7
Requirement levelNormal§ 4.4.2.2.3
Tensile strength for crackingMean tensile strength (4.4.1.3)§ 4.4.1.3
Limit for the long-term deflection: l divided by l/wadm300§ 4.4.3.1.1
Load factor for the permanent loads γG1.35
Load factor for the imposed load γQ1.5
Shape of the columnRectangular
Column side in the direction checked cx500 mm
Column side across cy500 mm
Tendons over the column in the other directionThe same as in this direction§ 4.3.6.2.6
Height of an anchor plate ah90 mm
Width of an anchor plate aw250 mm
Spacing of the anchors in the band sa500 mm
Links behind the anchors: diameter Øl12 mm
Links behind the anchors: spacing along the edge sl100 mm
Calculation: The slab
StepValueRef.
Largest spanl = 7.50 m
Slendernesspost-tensioned flat slabs commonly reach about 35 to 45l/h = 26.8
Area per metre of width1000·hac = 280,000 mm²/m
Section modulus per metre1000·h²/6the same at the top and the bottom; the core is the middle third of the thicknesswc = 13,066,667 mm³/m
Calculation: The design strip
StepValueRef.
Width of the design striply = 7.50 m
Width of the column striptakes 70 % of the support moment and 60 % of the span momentbc = 3.50 m
Width of the middle striptakes 30 % of the support moment and 40 % of the span momentbm = 4.00 m
Calculation: Ordinary reinforcement per metre
StepValueRef.
Bottom barsØ12 @ 200 mm, d = 250 mmas,b = 565 mm²/m
Top bars over the supports, column stripØ16 @ 150 mmas,t = 1,340 mm²/m
Top bars over the supports, middle stripØ12 @ 200 mmas,t,m = 565 mm²/m
Self-weightγ·hg0 = 7.00 kN/m²
Calculation: Prestressing steel
StepValueRef.
Tendons in the design stripnp = 4
Share in the column stripenteredηp = 0.75
Area of the prestressing steel in the stripnp·Ap1Ap = 2,400 mm²
Prestressing steel per metre, column stripηp·Ap/bcap,c = 514 mm²/m
Prestressing steel per metre, middle strip(1 − ηp)·Ap/bmap,m = 150 mm²/m
Design strengthfp0,1k/γsfpd = 1,426 N/mm²§ 2.4.2.5 (5)
Calculation: Tendon profile
StepValueRef.
Eccentricity at the low pointsh/2 − yMeM = 90 mm
Eccentricity at the edgesh/2 − yEeE = 0 mm
Eccentricity over the interior supportsh/2 − ySnegative: above mid-deptheS = -85 mm
Sag of the tendon in the first spanyE + ξ·(yS − yE) − yM, under the chord at the low pointf = 124 mm
Calculation: Check 1 — stress at tensioning
StepValueRef.
Stress in the prestressing steel during tensioningσp,max/limη = 0.945 · Pass95 % of the capacity used§ 4.1.5.2.1 (21)
Force at the jack, one tendonσp,max·Ap1Pmax,1 = 837.0 kN
Calculation: Friction along the tendon
StepValueRef.
Sum of the angular deviationsΣ|Δθ| over the whole tendon47.4°Σφ = 0.827 rad
Lowest force after friction, one tendonPmax·e^(−μ·(φx + Δφ·x))Pmin = 769.5 kN§ 4.1.5.3.3 (24)
Largest friction lossΔPμ/Pmax = 8.1 %
Calculation: Slip at the anchors
StepValueRef.
Length affected by the slip∫ 2·(P(x) − P(ls)) dx = Δls·Ep·Apat each endls = 9.69 m§ 4.1.5.3.1
Force at the anchor after the slip, one tendon2·P(ls) − P(0)PA = 712.6 kN
Calculation: Check 2 — stress after anchoring
StepValueRef.
Largest steel stress after anchoringσp/limη = 0.926 · Pass93 % of the capacity used§ 4.1.5.2.2 (22)
Calculation: Shortening of the concrete at transfer
StepValueRef.
Modular ratio at transferEp/Ecm(t)αp(t) = 6.50
Concrete stress at the tendon, x = 2.77 mP/Ac + P·e²/Ic − Mg0·e/Ic, the whole stripcompression positive hereσc,p = 1.61 N/mm²
Loss of steel stress(np − 1)/(2·np)·αp(t)·σc,p — tendons tensioned one after the otherΔσp,el = 3.9 N/mm²§ 4.1.5.3.1
Calculation: Time-dependent losses at x = 2.77 m
StepValueRef.
Relaxation loss, long term3·ρ1000·σp0Δσpr = 90.2 N/mm²§ 3.3.2.7.1
Concrete stress at the tendon, quasi-permanentP0 with g0 + g2 + ψ2·qcompression positive hereσc,QP = 1.06 N/mm²
Loss from creep, shrinkage and relaxation(εcs·Ep + 0.8·Δσpr + αp·φ·σc,QP)/(1 + αp·Ap/Ac·(1 + Ac·e²/Ic)·(1 + 0.8·φ))the material laws of 3.1.2.5 to 3.1.2.7 and 3.3.2.7 (4.1.5.3.4) combinedΔσp,c+s+r = 137.6 N/mm²EN 1992-1-1 (5.46)
Force after all losses / force at the jackP∞/Pmax = 76.4 %
Calculation: Forces at the key sections
Step1Left edgex = 0.00 m2Low point 1x = 2.77 m3Support 1x = 7.00 m4Low point 2x = 10.75 m5Support 2x = 14.50 m6Low point 3x = 18.73 m7Right edgex = 21.50 mRef.
Height of the tendon yp mm140502255022550140
Eccentricity e mmh/2 − yp, positive below mid-depth090-8590-85900
After friction, the strip Pμ kN3,3483,3023,1933,0783,1933,3023,348§ 4.1.5.3.3 (24)
After the slip, the strip Ps kN2,8502,8973,0063,0783,0062,8972,850§ 4.1.5.3.1
At transfer, the strip P0 kNafter the shortening of the concrete2,8432,8872,9963,0652,9962,8872,843
After all losses, the strip P∞ kN2,5002,5572,6602,7012,6602,5572,500§ 4.1.5.3.4
Mean compression of the concrete σcp N/mm²P∞/Ac1.191.221.271.291.271.221.19
Final steel stress σp∞ N/mm²P∞/Ap1,0421,0661,1081,1251,1081,0661,042
Calculation: Check 3 — final stress in the prestressing steel
StepValueRef.
Smallest stress after all losses at least 0.45·fpk0.45·fpk/σp∞η = 0.803 · Pass80 % of the capacity used§ 4.1.5.2.3
Calculation: Equivalent loads of the prestress
StepValueRef.
Upward load in span 1P∞·y″ at the low point, over the width lyu1 = 7.83 kN/m²§ 4.1.5.1.1
Share of the permanent load it balancesabout 70 to 100 % keeps the slab nearly flat under the permanent loadu/(g0 + g2) = 87 %
Upward load in span 2P∞·y″ at the low point, over the width lyu2 = 11.20 kN/m²§ 4.1.5.1.1
Share of the permanent load it balancesabout 70 to 100 % keeps the slab nearly flat under the permanent loadu/(g0 + g2) = 124 %
Upward load in span 3P∞·y″ at the low point, over the width lyu3 = 8.12 kN/m²§ 4.1.5.1.1
Share of the permanent load it balancesabout 70 to 100 % keeps the slab nearly flat under the permanent loadu/(g0 + g2) = 90 %
Calculation: Secondary moments of the prestress
StepValueRef.
Over support 1, after all lossesfrom the compatibility of the continuous strip under −P·eon the whole strip; linear between the supports, zero at the end supportsMP,s,∞ = 60.5 kNm§ 4.1.5.1.3
Over support 2, after all lossesfrom the compatibility of the continuous strip under −P·eon the whole strip; linear between the supports, zero at the end supportsMP,s,∞ = 60.5 kNm§ 4.1.5.1.3
Calculation: Check 1 — strength of the concrete at transfer
StepValueRef.
Strength at transfer at least 0.3·fck0.3·fck/fck(t)η = 0.420 · Pass42 % of the capacity used§ 4.1.5.2.4
Calculation: Stresses at transfer, column strip
StepValueRef.
Largest compression, outside the anchorage zonesbottom face, x = 10.75 m; compression negativeσc,0 = -4.73 N/mm²
Largest tensiontop face, x = 10.75 mσct,0 = 0.04 N/mm²
Calculation: Check 2 — concrete compression at transfer, column strip
StepValueRef.
Largest concrete compression at transfer, column strip|σc,0|/(0.6·fck(t))η = 0.316 · Pass32 % of the capacity used§ 4.1.5.2.4 (23)
Calculation: Stresses in service: P_∞, g_0 + g_2 + ψ_2·q, column strip
StepValueRef.
Largest compressionbottom face, x = 10.59 mσc,QP = -3.31 N/mm²
Largest tensionnone: decompressed nowhereσct,QP = -0.83 N/mm²
Calculation: Stresses at transfer, middle strip
StepValueRef.
Largest compression, outside the anchorage zonestop face, x = 3.50 m; compression negativeσc,0 = -1.15 N/mm²
Largest tensionnone: the whole slab is compressedσct,0 = -0.14 N/mm²
Calculation: Check 3 — concrete compression at transfer, middle strip
StepValueRef.
Largest concrete compression at transfer, middle strip|σc,0|/(0.6·fck(t))η = 0.077 · Pass8 % of the capacity used§ 4.1.5.2.4 (23)
Calculation: Stresses in service: P_∞, g_0 + g_2 + ψ_2·q, middle strip
StepValueRef.
Largest compressiontop face, x = 3.06 mσc,QP = -1.87 N/mm²
Largest tensionbottom face, x = 2.92 m: below fct,effσct,QP = 0.73 N/mm²
Calculation: Effective tensile strength
StepValueRef.
Effective tensile strengthkt·fctm, kt = 1/(1 + 0.5·h/3)fct,eff = 3.06 N/mm²§ 4.4.1.3
Calculation: Cracks in span 1, column strip, x = 2.92 m
StepValueRef.
Concrete stress at the bottom facecompressedσct = -1.62 N/mm²
Bar stress at first cracking — in span 1, column stripσs,r/fykη = 0.131 · Pass13 % of the capacity usedTable 17
Calculation: Cracks over support 1, column strip, x = 7.00 m
StepValueRef.
Concrete stress at the top facecompressedσct = -0.63 N/mm²
Bar stress at first cracking — over support 1, column stripσs,r/fykη = 0.091 · Pass9 % of the capacity usedTable 17
Calculation: Cracks in span 2, column strip, x = 10.75 m
StepValueRef.
Concrete stress at the bottom facecompressedσct = -3.30 N/mm²
Bar stress at first cracking — in span 2, column stripσs,r/fykη = 0.124 · Pass12 % of the capacity usedTable 17
Calculation: Cracks over support 2, column strip, x = 14.50 m
StepValueRef.
Concrete stress at the top facecompressedσct = -0.63 N/mm²
Bar stress at first cracking — over support 2, column stripσs,r/fykη = 0.091 · Pass9 % of the capacity usedTable 17
Calculation: Cracks in span 3, column strip, x = 18.58 m
StepValueRef.
Concrete stress at the bottom facecompressedσct = -1.62 N/mm²
Bar stress at first cracking — in span 3, column stripσs,r/fykη = 0.131 · Pass13 % of the capacity usedTable 17
Calculation: Cracks in span 1, middle strip, x = 2.92 m
StepValueRef.
Concrete stress at the bottom facetension below fct,eff: uncrackedσct = 0.73 N/mm²
Bar stress at first cracking — in span 1, middle stripσs,r/fykη = 0.381 · Pass38 % of the capacity usedTable 17
Calculation: Cracks over support 1, middle strip, x = 7.00 m
StepValueRef.
Concrete stress at the top facetension below fct,eff: uncrackedσct = 0.24 N/mm²
Bar stress at first cracking — over support 1, middle stripσs,r/fykη = 0.379 · Pass38 % of the capacity usedTable 17
Calculation: Cracks in span 2, middle strip, x = 10.75 m
StepValueRef.
Concrete stress at the bottom facecompressedσct = -0.16 N/mm²
Bar stress at first cracking — in span 2, middle stripσs,r/fykη = 0.374 · Pass37 % of the capacity usedTable 17
Calculation: Cracks over support 2, middle strip, x = 14.50 m
StepValueRef.
Concrete stress at the top facetension below fct,eff: uncrackedσct = 0.24 N/mm²
Bar stress at first cracking — over support 2, middle stripσs,r/fykη = 0.379 · Pass38 % of the capacity usedTable 17
Calculation: Cracks in span 3, middle strip, x = 18.58 m
StepValueRef.
Concrete stress at the bottom facetension below fct,eff: uncrackedσct = 0.73 N/mm²
Bar stress at first cracking — in span 3, middle stripσs,r/fykη = 0.381 · Pass38 % of the capacity usedTable 17
Calculation: Deflection of the design strip
StepValueRef.
Camber at transfer∬ (Mg0 + MP,0)/(Ecm(t)·Ic)upward; the prestress P0 with the self-weight, short termw0 = 1.1 mm
Long-term deflection of the loads alone(1 + φ)·∬ (Mg + ψ2·Mq)/(Ecm·Ic)without the prestress, for comparisonwg+ψq = 7.4 mm
Long-term deflection with the prestress(1 + φ)·∬ (Mg + ψ2·Mq + MP,∞)/(Ecm·Ic)uncracked gross section, creep by (1 + φ); negative: upwardw∞ = 2.4 mm§ 4.4.3.2.4 (103)
Calculation: Check 14 — long-term deflection, span 1
StepValueRef.
Long-term deflection, span 1|w∞|/wadmη = 0.103 · Pass10 % of the capacity used§ 4.4.3.2.1
Calculation: Check 15 — long-term deflection, span 2
StepValueRef.
Long-term deflection, span 2|w∞|/wadmη = 0.071 · Pass7 % of the capacity used§ 4.4.3.2.1
Calculation: Check 16 — long-term deflection, span 3
StepValueRef.
Long-term deflection, span 3|w∞|/wadmη = 0.103 · Pass10 % of the capacity used§ 4.4.3.2.1
Calculation: Design actions on the design strip
StepValueRef.
Largest sagging design momentγG·Mg + γQ·Mq + MP,sthe secondary moment of P∞ with γP = 1.0 (4.1.5.1.4); q on the spans that make it largestMd,max = 537.0 kNm§ 4.1.5.5.2
Largest hogging design momentγG·Mg + γQ·Mq + MP,sover an interior supportMd,min = -621.0 kNm§ 4.1.5.5.2
Calculation: Check 1 — bending in span 1, column strip, x = 2.92 m
StepValueRef.
Design moment per metreψf·Md/bcsaggingmd = 92.1 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 210.9 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 1, column stripMd/MRdη = 0.436 · Pass44 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 1, column stripMcr/MRdη = 0.570 · Pass57 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 1, column strip(x/d)/(0.5·435/fyd)η = 0.343 · Pass34 % of the capacity used§ 4.1.4.2.6
Calculation: Check 2 — bending over support 1, column strip, x = 7.00 m
StepValueRef.
Design moment per metreψs·Md/bchogging: the top in tensionmd = -124.2 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = -277.2 kNm/m§ 4.2.1.5
Design moment against the bending resistance — over support 1, column stripMd/MRdη = 0.448 · Pass45 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — over support 1, column stripMcr/MRdη = 0.433 · Pass43 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — over support 1, column strip(x/d)/(0.5·435/fyd)η = 0.495 · Pass50 % of the capacity used§ 4.1.4.2.6
Calculation: Check 3 — bending in span 2, column strip, x = 10.75 m
StepValueRef.
Design moment per metreψf·Md/bcsaggingmd = 62.4 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 211.1 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 2, column stripMd/MRdη = 0.296 · Pass30 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 2, column stripMcr/MRdη = 0.591 · Pass59 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 2, column strip(x/d)/(0.5·435/fyd)η = 0.343 · Pass34 % of the capacity used§ 4.1.4.2.6
Calculation: Check 4 — bending over support 2, column strip, x = 14.50 m
StepValueRef.
Design moment per metreψs·Md/bchogging: the top in tensionmd = -124.2 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = -277.2 kNm/m§ 4.2.1.5
Design moment against the bending resistance — over support 2, column stripMd/MRdη = 0.448 · Pass45 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — over support 2, column stripMcr/MRdη = 0.433 · Pass43 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — over support 2, column strip(x/d)/(0.5·435/fyd)η = 0.495 · Pass50 % of the capacity used§ 4.1.4.2.6
Calculation: Check 5 — bending in span 3, column strip, x = 18.58 m
StepValueRef.
Design moment per metreψf·Md/bcsaggingmd = 92.1 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 210.9 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 3, column stripMd/MRdη = 0.436 · Pass44 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 3, column stripMcr/MRdη = 0.570 · Pass57 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 3, column strip(x/d)/(0.5·435/fyd)η = 0.343 · Pass34 % of the capacity used§ 4.1.4.2.6
Calculation: Check 6 — bending in span 1, middle strip, x = 2.92 m
StepValueRef.
Design moment per metre(1 − ψf)·Md/bmsaggingmd = 53.7 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 106.6 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 1, middle stripMd/MRdη = 0.504 · Pass50 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 1, middle stripMcr/MRdη = 0.598 · Pass60 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 1, middle strip(x/d)/(0.5·435/fyd)η = 0.215 · Pass22 % of the capacity used§ 4.1.4.2.6
Calculation: Check 7 — bending over support 1, middle strip, x = 7.00 m
StepValueRef.
Design moment per metre(1 − ψs)·Md/bmhogging: the top in tensionmd = -46.6 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = -105.6 kNm/m§ 4.2.1.5
Design moment against the bending resistance — over support 1, middle stripMd/MRdη = 0.441 · Pass44 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — over support 1, middle stripMcr/MRdη = 0.604 · Pass60 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — over support 1, middle strip(x/d)/(0.5·435/fyd)η = 0.217 · Pass22 % of the capacity used§ 4.1.4.2.6
Calculation: Check 8 — bending in span 2, middle strip, x = 10.75 m
StepValueRef.
Design moment per metre(1 − ψf)·Md/bmsaggingmd = 36.4 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 106.6 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 2, middle stripMd/MRdη = 0.341 · Pass34 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 2, middle stripMcr/MRdη = 0.609 · Pass61 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 2, middle strip(x/d)/(0.5·435/fyd)η = 0.215 · Pass22 % of the capacity used§ 4.1.4.2.6
Calculation: Check 9 — bending over support 2, middle strip, x = 14.50 m
StepValueRef.
Design moment per metre(1 − ψs)·Md/bmhogging: the top in tensionmd = -46.6 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = -105.6 kNm/m§ 4.2.1.5
Design moment against the bending resistance — over support 2, middle stripMd/MRdη = 0.441 · Pass44 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — over support 2, middle stripMcr/MRdη = 0.604 · Pass60 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — over support 2, middle strip(x/d)/(0.5·435/fyd)η = 0.217 · Pass22 % of the capacity used§ 4.1.4.2.6
Calculation: Check 10 — bending in span 3, middle strip, x = 18.58 m
StepValueRef.
Design moment per metre(1 − ψf)·Md/bmsaggingmd = 53.7 kNm/m
Bending resistance per metrebars and bonded tendonsmRd = 106.6 kNm/m§ 4.2.1.5
Design moment against the bending resistance — in span 3, middle stripMd/MRdη = 0.504 · Pass50 % of the capacity used
Resistance above the cracking moment (minimum reinforcement) — in span 3, middle stripMcr/MRdη = 0.598 · Pass60 % of the capacity used§ 4.3.1.2
Compression zone shallow enough for a ductile section — in span 3, middle strip(x/d)/(0.5·435/fyd)η = 0.215 · Pass22 % of the capacity used§ 4.1.4.2.6
Calculation: Punching at support 1 (interior column)
StepValueRef.
Design support forceγG·Rg + γQ·Rq + RP,s, all spans loadedsecondary reaction of the prestress RP,s = -9 kNRd = 990 kN
Effective depthh − yt − Øt/2, between the two top layersdv = 242 mm§ 4.3.6.2.1
Control section at dv/2 from the column2·(cx + cy) + π·dvu0 = 2,760 mm§ 4.3.6.2.2
Reduction for the moment transferinterior column of a regular flat slabke = 0.90§ 4.3.6.2.5
Effective control sectionke·u0u = 2,484 mm§ 4.3.6.2.4
Load inside the control sectionqd·A = 9.0 kN§ 4.3.6.2.6
Vertical force of the tendons crossing the control sectionn·p∞·(cy + dv)·(sin βl + sin βr)this direction and the same assumed in the other; p∞ = 569.9 kN/m in the column strip, slope 2.6° at the sectionVP = 76.3 kN§ 4.3.6.2.6
Design punching forceRd − qd·A − VPVd = 905 kN§ 4.3.6.2.6
Distance to the point of zero moment0.22·l, the larger adjacent spanrs = 1,650 mm§ 4.3.6.4.4
Width of the support strip1.5·√(rsx·rsy) ≤ lmin, rsy = 0.22·lybs = 2,475 mm§ 4.3.6.4.6 (61)
Mean moment in the support stripVd·(1/8 + eu/(2·bs))eu = b·(1/ke − 1) = 92 mm, b the diameter of the area inside the control sectionmsd = 129.9 kNm/m§ 4.3.6.4.7 (62)
Bending resistance of the support striptop bars of the column strip and the tendonsmRd = 277.2 kNm/m§ 4.3.6.4.5
Decompression moment of the prestressp∞·(h/6 + es)es = 85 mm above mid-depth; P∞ after all lossesmDd = 75.0 kNm/m§ 4.3.6.4.3
Slab rotation1.5·(rs/dv)·(fyd/Es)·((msd − mDd)/(mRd − mDd))^1.5level 2; the other direction taken alikeψ = 0.0031§ 4.3.6.4.1 (60), 4.3.6.4.3
Design shear stress limit0.3·√fck/γcτcd = 1.183 N/mm²§ 2.4.2.4 (3)
Aggregate factor48/(16 + Dmax·min(1 ; (60/fck)²)) ≥ 1.2kg = 1.200§ 4.3.3.2.1 (37)
Factor for size, rotation and aggregate1/(0.45 + 0.18·ψ·dv·kg) ≤ 2kr = 1.638§ 4.3.6.3.2 (59)
Punching resistancekr·τcd·dv·uVRd,c = 1,165 kN§ 4.3.6.3.1 (58)
Calculation: Check — punching without punching reinforcement
StepValueRef.
Punching at the interior columnVd/VRd,cη = 0.776 · Pass78 % of the capacity used§ 4.3.6.3.1 (58)
Calculation: Design force at an anchor
StepValueRef.
Force at the jack, one tendonthe characteristic force of the overtensionPmax,1 = 837.0 kN
Design force for the anchorage zoneγP·Pmax,1, γP = 1.2Pd,1 = 1,004.4 kN§ 4.1.5.5.3
Design strength of the concrete at transferηfc·ηt·fck(t)/γcfcd(t) = 16.7 N/mm²§ 2.4.2.3 (2)
Bearing stress under the platePd,1/(ah·aw)against fcd(t) = 16.7 N/mm² for plain concreteσc0 = 44.6 N/mm²
Calculation: Bursting through the thickness
StepValueRef.
Height of the spreading prism2·min(yE ; h − yE)he = 280 mm
Bursting force at one anchor0.25·Pd,1·(1 − ah/he)strut-and-tie model of the spreading force, concrete tension neglectedTv = 170.4 kN§ 5.3.3
Bursting force per metre of edgeTv/sasa = 500 mm between the anchorstv = 340.8 kN/m
Links needed per metre of edgetv/fydvertical legs within he behind the edgeas,v = 784 mm²/m
Calculation: Check 1 — links against the bursting through the thickness
StepValueRef.
Bursting force against the linkstv/(as·fyd)η = 0.693 · Pass69 % of the capacity used§ 5.3.3
Calculation: Spreading in the plane of the slab
StepValueRef.
Splitting force between two anchors0.25·Pd,1·(1 − aw/sa)bars parallel to the edge, within sa behind itTh,1 = 125.6 kN§ 5.3.3
Width of the band of anchors(nb − 1)·sa + aw3 tendonsbb = 1,250 mm
Splitting force of the band spreading over the strip0.25·Pd,band·(1 − bb/ly)Pd,band = 1.2·Pmax of the bandTb = 628 kN§ 5.3.3
Bars parallel to the edge for TbTb/fydspread between about 0.1·ly and ly/2 behind the edgeAs,b = 1,444 mm²

How this module is verified

Verified clause by clause against SIA 262:2025 and against independent calculations used on real projects, before release.

Questions

Where should the tendons of a flat slab go?

Banded over the column line is the usual choice in one direction, with the other direction spread. The upward load of banded tendons acts in the column strip; the middle strips hang on it as on a beam.

How do the tendons help against punching?

The tendons crossing the control section slope down away from the column and carry part of the force, VP, to it. Their decompression moment mDd enters the slab rotation ψ through (msd − mDd)/(mRd − mDd), clause 4.3.6.4.3.

Which plan includes this module?

The Pro plan, with its calculation note.