Structural Engineering Tools

CLT floor panel: bending and rolling shear

Checks a cross-laminated timber (CLT) floor panel spanning one way at the ultimate limit state: bending on the layers that run along the span, and rolling shear in the cross layers. SIA 265 has no provisions for CLT; the partial factor and the modification factor k_mod come from EN 1995-1-1. Every step shows its formula and where it comes from.

Pro EN 1995-1-1

Part of the Pro plan

This module is included in the Pro plan and above, with its calculation note.

About this check

clauses, worked example and questions

Checks a cross-laminated timber (CLT) floor panel spanning one way at the ultimate limit state: bending on the layers that run along the span, and rolling shear in the cross layers. SIA 265 has no provisions for CLT; the partial factor and the modification factor k_mod come from EN 1995-1-1. Every step shows its formula and where it comes from.

What it checks

  • Net section of the panel: only the layers running along the span are credited with bending stiffness (A0,net, I0,net, W0,net); the cross layers carry the rolling shear.
  • Bending: σm,d = Md / W0,net ≤ fm,Rd = kmod · fm,k · ksys / γM.
  • Rolling shear: τv,R,d = 1.5 · Vz,d / (b · h) ≤ fv,R,Rd = kmod · fv,R,k / γM; ksys does not apply to rolling shear.
  • Modification factor kmod from EN 1995-1-1, table 3.1, by load duration and humidity class.

What you enter and what you get

You enter the lay-up (3, 5 or 7 layers, each thickness, numbered from the exposed face), the width considered (usually 1 m), the load duration and humidity class, the characteristic bending strength fm,k and rolling shear strength fv,R,k of the product, the system factor, the partial factor γM, and the design moment and shear force.

You get the net section properties, both checks with their utilisations, and every intermediate value with its source. With the Pro plan, it prints as an A4 calculation note.

Assumptions and limits

  • Panel spanning one way; the layers along the span carry bending, the cross layers are given no bending stiffness.
  • Rolling shear is taken over the full thickness of the panel.
  • The characteristic strengths of the CLT product are entered by you.
  • The deflection and vibration of the panel (its own module) and the fire situation (its own module) are separate.

Worked example

A five-layer panel 40-20-20-20-40 mm (140 mm), one metre wide, permanent actions in humidity class 2, f_m,k = 24 N/mm², f_v,R,k = 1.1 N/mm², k_sys = 1.1, γ_M = 1.25, with M_d = 12.09 kN·m and V_z,d = 12.09 kN. These are the module's own results for its worked example, computed when this page was built.

Inputs
InputValueRef.
Number of layers5
Layer 1, along the span d140 mm
Layer 1–2, across the span d1220 mm
Layer 2, along the span d220 mm
Layer 2–3, across the span d2320 mm
Layer 3, along the span d340 mm
Width considered b1000 mm
Load duration kmodPermanentEN 1995-1-1 t.3.1
Humidity class2EN 1995-1-1 t.3.1
Characteristic bending strength fm,k24 N/mm²
Characteristic rolling shear strength fv,R,k1.1 N/mm²
System factor ksys1.1
Partial factor γM1.25EN 1995-1-1
Design bending moment Md12.09 kN·m
Design shear force Vz,d12.09 kN
Calculation: Common values
StepValueRef.
Modification factorkmod = 0.50EN 1995-1-1 t.3.1
Total thickness of the panelthe sum of every layerh = 140.0 mm
Net area of the layers along the spanonly the layers running along the span are countedA0,net = 100,000 mm²
Position of the neutral axiszs = h / 2 for a symmetrical lay-upzs = 70.0 mm
Net second moment of areaΣ over the parallel layers of [b·d³/12 + b·d·(z − zs)²]. The cross layers are given no bending stiffness at all.I0,net = 211,333,333 mm⁴
Net section modulusW0,net = I0,net / zsW0,net = 3,019,048 mm³
Calculation: Check 1 — bending
StepValueRef.
Design bending strengthfm,Rd = kmod · fm,k · ksys / γMfm,Rd = 10.560 N/mm²EN 1995-1-1
Bending stressσm,d = Md / W0,netσm,d = 4.0046 N/mm²
Bendingσm,d ≤ fm,Rdη = 0.379 · Pass38 % of the capacity used
Calculation: Check 2 — rolling shear
StepValueRef.
Design rolling shear strengthfv,R,Rd = kmod · fv,R,k / γM. ksys does not apply to rolling shear.fv,R,Rd = 0.4400 N/mm²EN 1995-1-1
Rolling shear stressτ = 1.5 · Vz,d / (b · h), taken over the full thicknessτv,R,d = 0.1295 N/mm²
Rolling shearτv,R,d ≤ fv,R,Rdη = 0.294 · Pass29 % of the capacity used

How this module is verified

Verified step by step against the factors of EN 1995-1-1 and against independent calculations used on real projects, before release.

Questions

Why not SIA 265?

SIA 265 has no provisions for cross-laminated timber. The module uses the partial factor and the modification factor kmod of EN 1995-1-1, and says on each step where a value comes from.

Why does rolling shear govern CLT?

The cross layers are loaded across the grain in both directions at once. Their rolling shear strength is roughly a tenth of the shear strength along the grain.

Which plan includes this module?

The Pro plan, with its calculation note.

Related

Norm: EN 1995-1-1 · Page updated: 20 October 2026