Timber bearing in the fire situation to SIA 265

Checks the bearing of a solid-timber or glulam member on a support in the fire situation, to SIA 265:2021: the contact surface reduced by charring, and compression perpendicular to the grain on what remains. Every step shows its formula and the clause it comes from.

Basic SIA 265:2021

Part of the Basic plan

This module is included in the Basic plan and above, with its calculation note.

About this check

clauses, worked example and questions

Checks the bearing of a solid-timber or glulam member on a support in the fire situation, to SIA 265:2021: the contact surface reduced by charring, and compression perpendicular to the grain on what remains. Every step shows its formula and the clause it comes from.

What it checks

  • Charring: notional charring rate βn (clause 4.5.2.3, table 13), charring depth dchar,n = βn · t (clause 4.5.2.2, equation (50)) and effective loss of thickness def = dchar,n + dred (equation (49)).
  • Residual contact surface: how far the charring reaches into the bearing, from the side faces and the end of the member, depending on where the bearing sits, which faces are exposed, and whether the support is non-combustible or of timber. The time until the contact surface starts to lose area is given.
  • Resistance in fire, clause 4.5.2.5, equation (51): fRd,fi = 1.8 · fc,90,d · ηw.
  • Bearing in the fire situation: σc,90,d,fi = Rd,fi / Afi ≤ fRd,fi.
  • For comparison only, the resistance with the factor kfi of EN 1995-1-2 (not part of SIA 265).

What you enter and what you get

You enter the member (wood type, strength class, service class, width b), the type of support and the contact area, the strength fc,90,d from your copy of SIA 265, the design reaction in fire Rd,fi, whether the member was protected at the start of the fire, the material for charring, the fire exposure time, the zero-strength layer, the position of the bearing (at the end of the member or within the span), the overhang past the bearing, the exposed side faces, the gap to the bearing edge, and what the member bears on.

You get every step of the charring, the residual bearing length, width and area, the resistance and the utilisation with a pass or fail. With the Basic plan, it prints as an A4 calculation note.

Assumptions and limits

  • Rectangular members of solid timber or glulam; the charring model of SIA 265 clause 4.5.2.
  • No table of the norm is reproduced: you enter the strength from your own copy of SIA 265.
  • ηt, kh and ksys do not apply in the fire situation.
  • The ultimate limit state of the same bearing at normal temperature is its own module.

Worked example

The bearing of the ultimate-limit-state example (GL24h, 280 mm wide, bearing 280 × 280 mm at the end of the member, on concrete), unprotected, after 30 minutes of fire on both side faces, with a design reaction in fire of 22 kN. These are the module's own results, computed when this page was built.

Inputs
InputValueRef.
Wood typeGlulam
Strength classGL24h
Service class ηw1§ 3.2.1.3 t.4
Section width b280 mm
Type of supportGeneral§ 3.3.2.1 t.8 / 3.4.2.2 t.9
Contact area given byBearing length and width
Bearing length lA280 mm
Bearing width bA280 mm
Design compressive strength ⟂ grain fc,90,d1.9 N/mm²§ 3.3.2.1 t.8 / 3.4.2.2 t.9
Design support reaction in fire Rd,fi22 kN
Protected at the start of the fire?No
Material for charring βnSoftwood or beech — glulam§ 4.5.2.3 t.13
Fire exposure time t30 min
Zero-strength layer dred7 mm§ 4.5.2.2
Position of the bearingAt the end of the member
Overhang of the member past the bearing ee0 mm
Side faces of the member exposedBoth
Gap from the side face to the bearing edgeBearing centred on the width — computed
The member bears onConcrete, masonry or steel
Calculation: Fire situation
StepValueRef.
Notional charring rateβn = 0.70 mm/min§ 4.5.2.3 t.13
Charring depthdchar,n = βn · tdchar,n = 21.00 mm§ 4.5.2.2 (50)
Effective loss of thicknessdef = dchar,n + dreddef = 28.00 mm§ 4.5.2.2 (49)
Nearest charring face to a bearing edgemeasured to a side face of the member. The contact surface keeps its full size while def ≤ emin. Here it is zero, so the contact surface starts to lose area as soon as the fire begins, the bearing covering the whole width of the member.emin = 0.0 mm
Contact surface intact untildef(t0) = emin, the zero-strength layer included. The exposure of 30 min is past this, so the contact surface has started to lose area.t0 = 0.0 min
Residual bearing widthbA − 28.0 mm on both sidesbA,fi = 224.0 mm§ 4.5.2.2
Residual bearing lengthlA − 28.0 mm at the near edge − 0.0 mm at the far edgelA,fi = 252.0 mm§ 4.5.2.2
Residual contact areaAfi = bA,fi · lA,fiAfi = 56,448 mm²§ 4.5.2.2
Design resistance in firefRd,fi = 1.8 · fc,90,d · ηwfRd,fi = 3.420 N/mm²§ 4.5.2.5 (51)
Design stress in fireσc,90,d,fi = Rd,fi / Afiσc,90,d,fi = 0.390 N/mm²
Bearing in the fire situationσc,90,d,fi ≤ fRd,fiη = 0.114 · Pass11 % of the capacity used§ 4.5.2.5 (51)
Alternative including kfifRd,fi* = 1.5 · fc,90,d · ηw · kfi, kfi = 1.15Not part of SIA 265. Utilisation would be 11.9%.fRd,fi * = 3.277 N/mm²EN 1995-1-2

How this module is verified

Verified clause by clause against SIA 265:2021 and against independent calculations used on real projects, before release.

Questions

Why does the contact surface shrink when the support is concrete?

The member chars from its exposed faces. Where the bearing reaches the side faces or the end of the member, the charred depth there no longer carries load, so the contact surface loses that strip. A timber support also chars from its own faces.

Which design reaction do I enter?

The reaction from the accidental combination for fire, Rd,fi, from your own analysis.

Is this module free?

The fire situation is part of the Basic plan, with the calculation note of every module. The ultimate limit state of the bearing is free.