Timber compression and biaxial bending in the fire situation to SIA 265

Checks a rectangular solid-timber or glulam member under axial compression and bending about both axes in the fire situation, to SIA 265:2021: the residual section after charring, the cross-section where the member is held against buckling, and buckling with bending where it is not. Every step shows its formula and the clause it comes from.

Basic SIA 265:2021

Part of the Basic plan

This module is included in the Basic plan and above, with its calculation note.

About this check

clauses, worked example and questions

Checks a rectangular solid-timber or glulam member under axial compression and bending about both axes in the fire situation, to SIA 265:2021: the residual section after charring, the cross-section where the member is held against buckling, and buckling with bending where it is not. Every step shows its formula and the clause it comes from.

What it checks

  • Charring and residual section: βn (clause 4.5.2.3, table 13), dchar,n (clause 4.5.2.2, equation (50)), def (equation (49)), residual width and depth, Aef, Wy,fi and Wz,fi.
  • Resistances in fire, clause 4.5.2.5, equation (51): 1.8 · fc,0,d · ηw in compression and 1.8 · fm,d · ηw · km,fi in bending; kh and ksys do not apply.
  • Stabilised zone in fire, cross-section, clause 4.2.4.2, equation (22).
  • Unstabilised zone in fire, buckling about each axis, clause 4.2.8.5, equation (37), with kc on the residual section (buckling lengths unchanged by fire).
  • For comparison only, the interaction with the factor kfi of EN 1995-1-2 (not part of SIA 265).

What you enter and what you get

You enter the member, the strengths from your copy of SIA 265, the lateral support spacings, the buckling lengths, the design actions in fire Nd,fi, My,d,fi and Mz,d,fi, whether the member was protected at the start of the fire, the material for charring, the exposure time, the zero-strength layer and the exposed faces.

You get the residual section, the three checks with their utilisations, every intermediate value with its clause, and figures. With the Basic plan, it prints as an A4 calculation note.

Assumptions and limits

  • Rectangular sections; the charring model of SIA 265 clause 4.5.2.
  • The same fire actions are applied to both zones. Where they differ along the member, run the module a second time with the other set.
  • With fire on several faces, narrow sections are flagged (clause 4.5.2.4); heat accumulation is flagged, not calculated.
  • The ultimate limit state at normal temperature is its own module.

Worked example

The member of the ultimate-limit-state example (GL24h, b × h = 680 × 280 mm, service class 2), unprotected, after 60 minutes of fire on all four faces, with N_d,fi = 44 kN, M_y,d,fi = 94 kN·m and M_z,d,fi = 1 kN·m. In this example the cross-section check and the buckling check about y-y do not pass. These are the module's own results, computed when this page was built.

Inputs
InputValueRef.
Wood typeGlulam
Strength classGL24h
Service class ηw2§ 3.2.1.3 t.4
Section width b680 mm
Section depth h280 mm
Design compressive strength ∥ grain fc,0,d16 N/mm²§ 3.4.2.2 t.9
Characteristic compressive strength ∥ grain fc,0,k24 N/mm²§ Annexe B
Design bending strength fm,d16 N/mm²§ 3.4.2.2 t.9
Characteristic bending strength fm,k24 N/mm²§ Annexe B
Modulus of elasticity, 5% fractile E0,059600 N/mm²§ Annexe B
Lateral support spacing, bending about y-y ay6820 mm§ 4.2.9.3
Lateral support spacing, bending about z-z az6820 mm§ 4.2.9.3
Buckling length given byEntered directly
Buckling length about y-y lk,y6820 mm
Buckling length about z-z lk,z6820 mm
Design compressive force in fire Nd,fi44 kN
Design moment about y-y in fire My,d,fi94 kN·m
Design moment about z-z in fire Mz,d,fi1 kN·m
Protected at the start of the fire?No
Material for charring βnSoftwood or beech — glulam§ 4.5.2.3 t.13
Fire exposure time t60 min
Zero-strength layer dred7 mm§ 4.5.2.2
Exposed facestop, bottom, left, right
Calculation: Common values
StepValueRef.
Notional charring rateβn = 0.70 mm/min§ 4.5.2.3 t.13
Charring depthdchar,n = βn · tdchar,n = 42.00 mm§ 4.5.2.2 (50)
Effective loss of thicknessdef = dchar,n + dreddef = 49.00 mm§ 4.5.2.2 (49)
Residual widthbfi = 582.0 mm
Residual depthhfi = 182.0 mm
Notional residual sectionAef = bfi · hfiAef = 105,924 mm²§ 4.5.2.2 f.13
Section modulus about y-yWy,fi = 3,213,028 mm³
Section modulus about z-zWz,fi = 10,274,628 mm³
Compressive resistance in firefRd,C,fi = 1.8 · fc,0,d · ηw. kh and ksys do not apply.fRd,C,fi = 23.040 N/mm²§ 4.5.2.5 (51)
Bending resistance in fire, y-yfRd,m,y,fi = 1.8 · fm,d · ηw · km,y,fifRd,m,y,fi = 23.040 N/mm²§ 4.5.2.5 (51)
Bending resistance in fire, z-zfRd,m,z,fi = 23.040 N/mm²§ 4.5.2.5 (51)
Compressive stress in fireσc,0,d,fi = Nd,fi / Aefσc,0,d,fi = 0.4154 N/mm²
Bending stress in fire, y-yσm,y,d,fi = 29.2559 N/mm²
Bending stress in fire, z-zσm,z,d,fi = 0.0973 N/mm²
Note on the fire actionsThe same fire actions are applied to both zones. Where they differ along the member, run the module a second time with the other set.—
Calculation: Check 1 — stabilised zone, cross-section
StepValueRef.
Stabilised zone in fire, cross-section(σc/fc)² + σm,y/fm,y + σm,z/fm,z ≤ 1η = 1.274 · Fail127 % of the capacity used§ 4.2.4.2 (22)
Alternative including kfi, cross-section checkeach resistance taken as 1.5 · f · ηw · kfi with kfi = 1.15Not part of SIA 265. Shown for comparison only.interaction * = 1.3298EN 1995-1-2
Calculation: Check 2 — unstabilised zone, buckling about y-y
StepValueRef.
Slenderness in fire, y-ybuckling lengths are unchanged by fireλy,fi = 129.663
Relative slenderness in fire, y-yλrel,y,fi = 2.0636§ 4.2.8.4 (34)
Auxiliary factor in fire, y-yk = 0.5 · [1 + βc·(λrel − 0.3) + λrel²]ky,fi = 2.7175§ 4.2.8.2 (31)
Buckling coefficient in fire, y-ykc = 1 / (k + √(k² − λrel²))kc,y,fi = 0.2229§ 4.2.8.2 (30)
Unstabilised zone in fire, buckling about y-yσc/(kc,y·fc) + σm,y/(km,y·fm) ≤ 1η = 1.351 · Fail135 % of the capacity used§ 4.2.8.5 (37)
Calculation: Check 3 — unstabilised zone, buckling about z-z
StepValueRef.
Slenderness in fire, z-zbuckling lengths are unchanged by fireλz,fi = 40.547
Relative slenderness in fire, z-zλrel,z,fi = 0.6453§ 4.2.8.4 (34)
Auxiliary factor in fire, z-zk = 0.5 · [1 + βc·(λrel − 0.3) + λrel²]kz,fi = 0.7255§ 4.2.8.2 (31)
Buckling coefficient in fire, z-zkc = 1 / (k + √(k² − λrel²))kc,z,fi = 0.9461§ 4.2.8.2 (30)
Unstabilised zone in fire, buckling about z-zσc/(kc,z·fc) + σm,z/(km,z·fm) ≤ 1η = 0.023 · Pass2 % of the capacity used§ 4.2.8.5 (37)

How this module is verified

Verified clause by clause against SIA 265:2021 and against independent calculations used on real projects, before release.

Questions

Which actions do I enter for the fire situation?

The actions of the accidental combination for fire from your own analysis. For floors in categories A and B, 0.6 times the actions at normal temperature may be assumed.

Is this module free?

The fire situation is part of the Basic plan, with the calculation note of every module. The ultimate limit state is free.

Related

Norm: SIA 265:2021 · Page updated: 20 October 2026